Reference | Description | Rating | Input voltage | Output voltage |
---|---|---|---|---|
TTH1 | Medical isolation transformer | 1 kVA | 400 V + N | 230 V + N |
TTH2 | Medical isolation transformer | 2 kVA | 400 V + N | 230 V + N |
TTH3.15 | Medical isolation transformer | 31,5 kVA | 400 V + N | 230 V + N |
TTH4 | Medical isolation transformer | 4 kVA | 400 V + N | 230 V + N |
TTH5 | Medical isolation transformer | 5 kVA | 400 V + N | 230 V + N |
TTH6.3 | Medical isolation transformer | 6,3 kVA | 400 V + N | 230 V + N |
TTH8 | Medical isolation transformer | 8 kVA | 400 V + N | 230 V + N |
TTH10 | Medical isolation transformer | 10 kVA | 400 V + N | 230 V + N |
Three Phase Cast Resin Medical Isolation Transformer (IEC/EN 61558-2-15)
Three Phase Cast Resin Medical Isolation Transformer
- Protection against corrosive environments
- Suitable for elevated vibration levels
- No damange of wire isolation due to current peaks
- Reduction of noise and internal vibrations
Input 400 V · Output 230 V.
Series:
TTH
Advantages of cast resin technique:
- Protection against corrosive environments
- Suitable for elevated vibration levels
- No damange of wire isolation due to current peaks
- Reduction of noise and internal vibrations
PRODUCTS IN THIS FAMILY
DIMENSIONS AND WEIGHTS
Reference | Description | Rating | Dimensions mm | Weight kg | ||||||
---|---|---|---|---|---|---|---|---|---|---|
A | B | C | D | E | Ø | |||||
TTH1 | Medical isolation transformer | 1 kVA | 280 | 138 | 205 | 80 | 250 | 9 | 24.4 | |
TTH2 | Medical isolation transformer | 2 kVA | 280 | 158 | 205 | 100 | 250 | 9 | 31.1 | |
TTH3.15 | Medical isolation transformer | 31,5 kVA | 340 | 150 | 255 | 96 | 310 | 9 | 42.3 | |
TTH4 | Medical isolation transformer | 4 kVA | 340 | 160 | 255 | 106 | 310 | 9 | 46.8 | |
TTH5 | Medical isolation transformer | 5 kVA | 340 | 200 | 255 | 126 | 310 | 9 | 59 | |
TTH6.3 | Medical isolation transformer | 6,3 kVA | 340 | 205 | 255 | 136 | 310 | 9 | 65 | |
TTH8 | Medical isolation transformer | 8 kVA | 410 | 195 | 305 | 116 | 380 | 11 | 81 | |
TTH10 | Medical isolation transformer | 10 kVA | 410 | 240 | 305 | 136 | 380 | 11 | 99 |
TECHNICAL CHARACTERISTICS
Isolation | Class F - 155ºC |
Winding | Class HC - 200ºC |
Leakage current | < 0,5 mA secondary-earth < 3,5 mA cover-earth |
Cover | Cast resin |
Frequency | 50-60 Hz |
Protection degree | IP-20 |
Connection group | YNyn0 |
Includes | Electrostatic screen betweeen primary and secondary Bimetal thermal protection |
Standards | IEC/EN 61558-1 / 61558-2-15 CE |
Safety class | Class I |
Test voltage | 4,5 kV (1 min, 50 Hz) |
To find out more about the Medical Transformers from Polylux, you can download here the documentation.